- Home
- Protudimne zavjese
Protudimne zavjese
- SMOKEBARRIER ST - Textile static smoke barrier (SSB)
Fire resistence : D120
The textile static smoke barrier SMOKEBARRIER ST is designed to divide the building in smoke zones in case of fire, and prevents consequential smoke spread to other areas.
Textile static smoke barriers are advantageous for minimal demands on the space and can be adapted very easily to all sorts of shapes and running technological installation.The main quality required is the fire resistance of these shutters.
Textile static smoke barriers SMOKEBARRIER ST have fire resistance D 60,
(the device is designed in accordance with CSN EN 12101-1).Certification:
The textile static smoke barrier SMOKEBARRIER ST was successfully tested in the FIRES s.r.o. test institute, and was granted CE certificate No. 1396-CPD-0028.
Technical characteristics:
- The barrier is made of a special fire-resistant textile, filled up with glass fibres with surface treatment (0.4 mm thickness), the textile can have silver-grey or white colour.
- The design of the barrier enables assembly without any additional special structures, fixation in concrete, masonry or steel profiles.
- The textile can be connected in a line, and thus an unlimited length of barriers can be created.
- The barriers have a very low weight (textile = 0.45kg/m2).
- All visible steel parts of the barriers are painted in a shade according to RAL sampler.
- SMOKEBARRIER AT - Textile active smoke barrier (ASB1/ASB3)
Fire resistence : D120
The textile active smoke barrier SMOKEBARRIER AT is designed to divide the building in smoke zones in case of fire, and prevents consequential smoke spread to other areas. The barrier is designed as a vertically sliding shutter.
This active smoke barrier is advantageous for minimum spatial requirements, since under normal conditions it is coiled in a cover that is placed in such a manner not to obstruct normal operation (usually above the floor).
The main quality required from these smoke barriers is their fire resistance. Textile active smoke barriers SMOKEBARRIER AT have fire resistance D 60 (the device is designed in accordance with EN 12101-1).
Certification:
This smoke barrier SMOKEBARRIER AT was successfully tested in the FIRES s.r.o. test institute, and was granted the CE certificate No. 1396-CPD-0027.
Technical characteristics:
- The shutter is made of a special fire-resistant textile, filled up with glass fibres with surface coating (0.4 mm thickness). White or grey color.
- The design allows the shutter to be placed on an opening or into it (or combination of both variants, as the case may be), without any additional special structures, fixation in concrete, masonry or steel profiles.
- The shutter can be connected in a line, which can create unlimited lengths of barriers.
- The standard dimension of the winding box is 150 x 158 mm, for bigger barrier dimensions the size of the box is 150 x 405.
- The smoke barrier is controlled electrically by means of a tube drive (electric motor with gearbox and gravitation start-up).
- It allows automatic closing from the fire alarm system switchboard (potential-free contact), even in case the supply voltage by means of gravitation drops out.
- Electronic control of individual functions of the smoke barrier proceeds by means of a special AOP control unit, including control elements (buttons or key control).
- Local autonomous fire sensors, optical and acoustic signalling can be supplied together with the shutter.
- Textile shutters have a very low weight (textile = 0.45kg/m2).
- The speed of the shutter closing is approx. 100 mm/s.
- All visible steel parts of the barriers are painted in a shade according to the RAL sampler.